Description
Industry Description
SIEMENS LOW VOLTAGE VL UL LISTED MOLDED CASE CIRCUIT BREAKER WITH THERMAL - MAGNETIC TRIP UNIT. BREAKER NNG FRAME WITH NORMAL BREAKING CAPACITY. 1200A 3-POLE (25KAIC AT 600V) (35KAIC AT 480V). INTERCHANGEABLE TRIP UNIT. EXTERNAL CONNECTIONLINE AND LOAD LUGS (TA4 NG500) WIRE RANGE 1/0AWG - 500KCMIL (CU/AL). DIMENSIONS(W x H x D) IN 9 x 16 x 6.2.
Modified Industry Description
BRKR VL NNG 3P 1200A LUG
AD Description
Siemens NNG3B120L VL Series Low Voltage Molded Case Circuit Breaker With Lugs, 600 VAC, 1200 A, 35 kA Interrupt, 3 Poles, Thermal Magnetic/LI Trip
Vendor Description
Siemens VL molded case circuit breakers utilize a compact and modular design which can be configured to suit a wide range of ratings from 30 A up to 1600 A. Designed for global requirements, most breakers include the world's major standards and markings such as UL, CSA, NOM, IEC, CE and CCC. At 480 VAC, VL circuit breakers feature N-Class (35kA), H-Class (65 kA) and L-Class (100 kA) interrupting ratings. They also feature both thermal magnetic and electronic trip units across the entire product line, assuring compatibility for virtually any application. VL trip units measure true RMS current. This type of measurement ensures the most accurate means of measuring currents in today's harmonic filled electrical distribution systems.
Specifications
| Amperage Rating |
1200
|
|---|---|
| Application |
GLOBAL INTERCHANGEABLE
|
| Connection |
LINE & LOAD STANDARD (CU/AL) LUGS
|
| Country of Origin |
MX
|
| Dimensions |
16 in H x 9 in W x 6.2 in D
|
| Frame |
NG
|
| Frequency_Rating |
50/60
|
| Interrupt_Rating |
35
|
| Material |
MOLDED CASE CIRCUIT BREAKER
|
| Number_Of_Poles |
3
|
| Operating_Temperature |
40DEGC
|
| Phase |
3-Phase
|
| Series |
VL Series
|
| Special Features |
|
| Standard |
UL/IEC/CE/CSA/NOM/CCC
|
| Sub_Brand |
VL
|
| Temperature_Rating |
40
|
| Type |
Low Voltage
|
| Voltage Rating |
600
|