Description
Industry Description
Hubbell Wiring Device, Power Protection Products, Receptacle, GFCI,Safety Grade Commercial Hospital Grade, Self Test, LED Indicator, 20A125V, 2-Pole 3-Wire Grounding, 5-20R, Brown
Modified Industry Description
20A/125V INDL. HG TAMPER ST GFCI,
AD Description
Wiring Device-Kellems AUTOGUARD® Style Line GFR8300SG Decorator Duplex Heavy Duty Standard Self-Test Tamper/Weather-Resistant GFCI Receptacle With LED Indicator, 125 VAC, 20 A, 2 Poles, 3 Wires, Brown
Vendor Description
Hubbell AUTOGUARD GFCI receptacles continually test and monitor for people protection capability automatically. This patented safety feature includes disconnecting power to the receptacle if critical components are damaged and GFCI protection is lost. GFCI auto-monitoring is conducted continuously within every 30 seconds. Also, clear visual indicators are provided on the device face representing power status, trip condition, ground fault condition and end of life status. In addition, for added safety, power will be denied to the receptacle face if reverse wiring of line and load was to occur.
Specifications
| Amperage Rating |
20
|
|---|---|
| Application |
Hospital Grade
|
| Color |
Brown
|
| Connection |
Back and Side Wired Screw Terminals
|
| Conductor Size |
#14 AWG to #12 AWG
|
| Country of Origin |
KR
|
| Environmental_Conditions |
Indoor Dry unless Protected by Additional Means
|
| Material |
Thermoplastic
|
| Mounting |
Screw Mount
|
| NEMA_Rating |
5-20R
|
| Number_Of_Poles |
2
|
| Phase |
1
|
| Series |
Hospital Grade
|
| Size |
Standard Sized Product
|
| Special Features |
|
| Standard |
NEMA WD1 and WD5, UL 498 and UL 943
|
| Sub_Brand |
Hubbell Wiring Device-Kellems
|
| Type |
Decorator Duplex
|
| Voltage Rating |
125
|
| Wattage |
2,500
|