Skip to main content

Siemens Siemens FD63B175

Image not found

Description

Industry Description

SIEMENS LOW VOLTAGE SENTRON MOLDED CASE CIRCUIT BREAKER WITH THERMAL - MAGNETICTRIP UNIT. UN-ASSEMBLED STANDARD 40 DEG C BREAKER FD FRAME WITH STANDARD BREAKING CAPACITY. 175A 3-POLE (22KAIC AT 600V) (35KAIC AT 480V). INTERCHANGEABLE TRIPUNIT. SPECIAL FEATURES LINE AND LOAD SIDE LUGS (TA1FD350A) WIRE RANGE 6AWG - 350KCMIL (CU) / 4AWG - 350KCMIL (AL). DIMENSIONS (W x H x D) IN 4.50 x 9.5 x 4.00.

Modified Industry Description

250AF 175AT 3P 600V ST-IC

AD Description

Siemens Sentron™ FD63B175 Type FD6 Low Voltage Molded Case Circuit Breaker, 600 VAC/500 VDC, 175 A, 22 kA Interrupt, 3 Poles, Thermal Magnetic Trip

Vendor Description

Siemens Sentron™ series circuit breakers have a long history of excellent performance in both the commercial and industrial market segments, they are tried and true in the most critical applications. Siemens Sentron™ series circuit breakers are available in nine frame sizes from 125 to 2000 A.

Specifications

Actuator
Varying
Amperage Rating
175
Auxiliary_Contacts
N/A
Brand Name
Siemens
Connection
N/A
Country of Origin
MX
Enclosure
Varying
Environmental_Conditions
N/A
Frame
FD6
Frequency_Rating
50/60
Interrupt_Rating
22
Material
N/A
Number_Of_Poles
3
Operating_Temperature
40C
Phase
3
Special Features

  • Actuator varying
  • Blue label
  • Enclosure varying
  • Molded case circuit breakers are used in motor circuits as a disconnecting means and for short circuit protection
  • The circuit breaker should have a continuous current rating of not less than 115% of the motor full load current
  • They should be used in conjunction with motor running, over-current-protection devices and should permit the motor to start without nuisance tripping from motor-inrush current

Standard
UL/HACR
Sub_Brand
Siemens
Trip_range
900 to 2000
Trip_Type
Thermal Magnetic
Type
Low Voltage
Voltage Rating
600 VAC/500 VDC

Recently Viewed Products

Loading recently viewed products...
Loading product details...