Skip to main content

Bussmann Bussmann LPJ-2SP

482440.jpg

Description

Industry Description

2A 600V Class J Low Peak Dual Element, Time Delay Fuse

Modified Industry Description

2A 600V - CLASS J LOW PEAK DUAL ELEMENT TIME DELAY FUSE

AD Description

Bussmann Low-Peak™ LPJ-2SP Current Limiting Time Delay Fuse, 2 A, 600 VAC/300 VDC, 300/100 kA, Class J, Cylindrical Body

Specifications

Amperage Rating
2
Application
Branch Circuit Breaker Panelboard Mains, Industrial Control, Machinery Disconnects, Power Panelboards
Brand Name
Bussmann
Characteristics
Time Delay
Connection
Ferrule End X Ferrule End
Country of Origin
MUL
Element
Dual
Interrupt_Rating
300/100
Material
Melamine
Model
LPJ
Package_Quantity
10
Response_Time
10
Size
0.81 In Diameter X 2.25 In Length
Special_Features

  • Consistent 2:1 ampacity ratios for all Low-Peak® fuses make selective coordination easy
  • Current limitation protects downstream components against damaging thermal and magnetic effects of short circuit currents
  • Dual element fuses have lower resistance than ordinary fuses, hence they run cooler
  • Fast short circuit protection and dual element, time delay performance provide ultimate protection
  • Industry's only UL listed and CSA Certified fuse with a 300 kA interrupt rating that allows for simple, worry free installation in virtually any application
  • Long time delay minimizes needless fuse openings due to temporary overloads and transient surges
  • Proper sizing can provide "No Damage" type 2 coordinated protection for NEMA® and IEC® motor controllers
  • Reduces existing fuse inventory by up to 33% when upgrading to Low-Peak® fuses
  • Selective coordination ratio of 2:1 (within Low-Peak® fuse family) prevents electrical shutdowns from extending beyond the failed circuit
  • Separate overload and short circuit elements provide time delay for sizing of high inrush loads linked with class J current limitation
  • Series combination ratings with branch circuit breakers allows broad range of coverage, independent of breaker manufacturer
  • Space saving package for equipment down sizing
  • They can often be sized for back up protection against motor burnout from overload or single phasing if other overload protective devices fail

Standard
UL, CSA C22.2, CE
Sub_Brand
Cooper Bussmann
Type_Of_Indicators
Non-Indicating
Type
Current Limiting
Voltage Rating
600 VAC/300 VDC