Description
Industry Description
Buck Boost Transformers, 5.0 KVA, Maximum Secondary Amperage: 208 at 24V, 104 at 48V, 240 x 480 Volt Primary, 24/48 Volt Secondary
Modified Industry Description
5KVA 240X480-24/48 BB
AD Description
SolaHD HS22F5A Encapsulated Buck Boost Transformer, 240 x 480 VAC Primary, 24/48 VAC Secondary, 5 kVA Power Rating, 60 Hz, 1 Phase
Vendor Description
Buck-boost transformers are small, 1-phase, dry-type distribution transformers designed and shipped as insulating/isolating transformers. They have a dual voltage primary and a dual voltage secondary. These transformers can be connected for a wide range of voltage combinations. The most common use is to buck (lower) or boost (raise) the supply voltage a small amount, usually 5 to 27%. Buck-boost transformers are in compliance with NEC article 210.9, exception 1, when field connected as an autotransformer.
Specifications
| Boost_Voltage |
200-240 , 458-480
|
|---|---|
| Brand Name |
SolaHD
|
| Buck_Voltage |
277-230 , 528-480
|
| Country of Origin |
US
|
| Frequency_Rating |
60
|
| Maximum_Amperage_Rating |
208/104
|
| Maximum_Input_Current |
41.6/83.3
|
| Number_Of_Channels |
240x480 Volts Primary, 24/48 Volts Secondary
|
| Phase |
1
|
| Power_Rating |
5
|
| Primary_Voltage |
240/480
|
| Secondary_Voltage |
24/48
|
| Special Features |
|
| Standard |
cULus Listed: UL 506, CSA C22.2 No.66
|
| Sub_Brand |
SolaHD
|
| Type |
Encapsulated
|
| Wattage |
2,000
|