CMC INDUSTRIAL FIXED SERIES PFC CAPACITORS

Power factor correction capacitor SI AMC

General

The CMC Series capacitor design incorporates high quality three phase cells which are vacuum-impregnated metallized polypropylene filled and hermetically sealed in a rugged steel welded case. This series of power factor correction capacitors is suitable for low voltage linear applications

Construction

The three phase cells which are used in the construction of the power factor banks are drawn steel rectangular cans which are vacuum-impregnated with a dielectric fluid to give added insulation, excellent corona protection, and a moisture barrier. The single and multiple assembly capacitor cell design units come with a manufactured 16 gauge steel weatherproof cover, and they have provision for floor, wall, or ceiling mounting pedestals. The single cell units come equipped with main lug connection, and the multiple assembly units incorporate a copper buss arrangement with a main lug connection.

Capacitor Cell Design

  • The dielectric fluid used in the capacitor cells is a green Non-PCB, non-toxic, biodegradable, and Class III combustible fluid.
  • Self-healing technology in case of overload, the self-healing properties of the low loss metallized polypropylene will prevent permanent dielectric breakdown.
  • Internal Pressure-Sensitive Interrupter which safely removes the capacitor from service at the end-of-life or under heavy fault conditions while still maintaining the integrity of the steel casing.
  • Internal resistors discharge voltage is less than 50 volts in less than 1 minute after the cell has electrically been removed from circuit.
  • Standards – UL810, C22.2 No. 190 Canadian Standards, ANSI/IEEE 18, IEC 831, NEMA CP-1, UL Recognized CYTW2, and cUL Recognized CYTW8

Capacitor Losses

The capacitor design has a total loss which is less than .5 Watts per kVAR at 60 HZ 25 degrees C.

Electrical CHaracteristics

  • 240 VAC, 480 VAC, 600 VAC rated Voltage at 60 HZ
  • The three phase capacitor internal connection is Delta.
  • Capacitance Tolerance is + or – 15%.
  • Overcurrent Tolerance is 135% of rated current continuously.
  • Overvoltage Tolerance is 110% of rated voltage
  • Standard Operating Temperature is -40 F to +115 F. Operation above 115 F will shorten the capacitor life.

Wiring Cable Insulation

All internal conductors are insulated stranded copper wire rated at 90 C.

Fuse Protection & Indicator Lights (Optional - Add Suffix Letter "L" to Catalog Number)

The internal protection fuses are time-delay and rated at 600 VAC with the sizing based upon the nominal amperage rating of the kVAR size in accordance with the National Electric Code requirements.

WARRANTY

1-YEAR WARRANTY on the capacitor cells

  • For single phase applications change Prefix Number from 3 to 1.
  • For 208 VAC applications divide kVAR size by .75 to find equivalent in 240 VAC size.
kVAR240 VAC Catalog Number480 VAC Catalog Number600 VAC Catalog Number
25324025CMC348025CMC360025CMC
30324030CMC348030CMC360030CMC
50324050CMC348050CMC360050CMC
60324060CMC348060CMC360060CMC
75324075CMC348075CMC360075CMC
90324090CMC348090CMC360090CMC
1003240100CMC3480100CMC3600100CMC
1203240120CMC3480120CMC3600120CMC
1253240125CMC3480125CMC3600125CMC
1503240150CMC3480150CMC3600150CMC
2003240200CMC3480200CMC3600200CMC
2503240250CMC3480250CMC3600250CMC
3003240300CMC3480300CMC3600300CMC
3503240350CMC3480350CMC3600350CMC
4003240400CMC3480400CMC3600400CMC
4503240450CMC3480450CMC3600450CMC
5003240500CMC3480500CMC3600500CMC
5503240550CMC3480550CMC3600550CMC
6003240600CMC3480600CMC3600600CMC